TN-S/TN-C-S systems
Type 1 or combined Type 1+2 SPDs are placed at the service entrance for the incoming supply (main distribution board). These devices protect against the effect of lightning electromagnetic impulses. The devices are ALWAYS connected in the x+0 (or CT1 format), with phase and neutral conductors connected to earth via the SPD.
In the case of Type 2 protectors located at downstream sub-distribution boards, a choice can be made:
- The SPD can be in the x+0 (CT1 connection type) – to further reduce the effects of lightning electromagnetic impulses, or it can be
- Connected in the x+1 (CT2 connection type) to restrict transient overvoltage generated internally, for example, from switching overvoltages.
In commercial and residential buildings it is better to select Type 2 SPDs in the x+0 mode, but in industrial complexes, due to switching overvoltages, it is better to select the x+1 (CT2 type).
Devices installed before the neutralising point in TN-C-S (4 wire) would require 3+0. Devices to be installed after the neutralising point (5 wire) would require 4+0.
TN-C system
In TN-C systems, Type 1, combined Type 1+2 and Type 2 protectors can only be connected in the x+0 format.
TT system
TT supply networks, in which only neutral conductors – L1, L2, L3 – are routed from the power source.
All protector types should ALWAYS be connected in the x+1 format.